False alarms in
Redbridge.

London Fire Brigade attended 851 automatic fire alarm false alarms in Redbridge in 2025, 2.3 a day. That ranks it 25th of London’s 33 areas.

Rank in London, 2025

25of 33

1 is the area with the most,
33 the area with the fewest

  • 851 attended in 2025
  • 2.3 a day, on average
  • 1.8% of the London total
851
AFA false alarms attended in 2025
667 residential, 184 non-residential
2.3
a day, on average
London: 128.9 a day
-3.4%
change on 2024
30 fewer than the 881 in 2024
-46.9%
daytime non-residential attendance
year after the 2024 policy change against the year before

What is counted. Incidents London Fire Brigade attended in Redbridge and recorded as a false alarm from an automatic fire alarm. Alarms that sounded and were not attended are not in the data. How the Index is built.

Redbridge · 2019 to 2025

25th of 33
in London.

London Fire Brigade attended 851 automatic fire alarm (AFA) false alarms in Redbridge in 2025. That is 1.8% of the London total and places it 25th of 33 areas. They made up 26.3% of everything the Brigade attended in the borough, below the London figure of 34.1%. The count is not adjusted for population or for the number of buildings.

The 2025 total was 30 lower than in 2024 (-3.4%). The highest year in the series was 2024, with 881, and the lowest was 2020, with 601.

From 1 January to 31 July 2026 the Brigade attended 486 AFA false alarms in Redbridge, against 470 in the same dates of 2025 (+3.4%, a smaller rise than London’s +10.0%). 2026 is a part year and should not be set against a full one.

AFA false alarms attended in Redbridge, 2019 to 2025

By calendar year of the 999 call. 2026 covers 1 January to 31 July 2026 only and is drawn paler.

  • Residential (dwellings and other residential)
  • Non-residential
  • Part year
Stacked column chart of automatic fire alarm false alarms attended in Redbridge each year from 2019 to 2025, split into residential and non-residential property, with 2026 shown separately as a part year. 2025: 851. Highest year: 2024 with 881.02505007501,0002019: 702 in total. non-residential 239, residential 46370220192020: 601 in total. non-residential 175, residential 42660120202021: 704 in total. non-residential 236, residential 46870420212022: 725 in total. non-residential 285, residential 44072520222023: 865 in total. non-residential 324, residential 54186520232024: 881 in total. non-residential 319, residential 56188120242025: 851 in total. non-residential 184, residential 66785120252026 to 31 Jul: 486 in total. non-residential 97, residential 3884862026to 31 Jul
Stacked column chart of automatic fire alarm false alarms attended in Redbridge each year from 2019 to 2025, split into residential and non-residential property, with 2026 shown separately as a part year. 2025: 851. Highest year: 2024 with 881.02505007501,0002019: 702 in total. non-residential 239, residential 46370220192020: 601 in total. non-residential 175, residential 42620202021: 704 in total. non-residential 236, residential 46820212022: 725 in total. non-residential 285, residential 44020222023: 865 in total. non-residential 324, residential 54120232024: 881 in total. non-residential 319, residential 56188120242025: 851 in total. non-residential 184, residential 66785120252026 to 31 Jul: 486 in total. non-residential 97, residential 3884862026to 31 Jul
Show the numbers as a table
AFA false alarms attended by London Fire Brigade in Redbridge, by period.
PeriodAFA false alarmsResidentialNon-residentialPer dayRank of 33Change
2019 702 463 239 1.9 29 +11.3%
2020 601 426 175 1.6 30 -14.4%
2021 704 468 236 1.9 29 +17.1%
2022 725 440 285 2.0 30 +3.0%
2023 865 541 324 2.4 26 +19.3%
2024 881 561 319 2.4 27 +1.8%
2025 851 667 184 2.3 25 -3.4%
2026, 1 January to 31 July 2026 486 388 97 2.3 25 +3.4%
Incidents attended, not alarm activations. The number on each column is the total for the period. The source has no incidents dated 31 December 2023. Source: London Fire Brigade Incident Records, London Datastore. Analysis: Gemini AMPM.
The policy change · 29 October 2024

Daytime attendance
at workplaces: -46.9%.

Since 29 October 2024 London Fire Brigade has not attended automatic fire alarms at most non-residential buildings between 07:00 and 20:30 unless a person also calls 999 to report a fire. Homes, schools, hospitals and the other premises on its exemption list still get a response at any hour.

In the year before London Fire Brigade changed its response on 29 October 2024, it attended 239 AFA false alarms at non-residential buildings in Redbridge between 07:00 and 20:30. In the year after it attended 127 (-46.9%). That is a smaller fall than London’s -53.4%, and ranks 26th of the 33 areas by size of fall. Residential attendances, which the policy does not affect, rose from 558 to 631 (+13.1%) over the same two years.

Before and after in Redbridge

AFA false alarms attended. Year before: 29 October 2023 to 28 October 2024. Year after: 29 October 2024 to 28 October 2025.
GroupYear beforeYear afterChange%
Non-residential, 07:00 to 20:30 239 127 -112 -46.9%
Property types not named as exempt 129 45 -84 -65.1%
Hospitals, schools, nurseries, prisons 110 82 -28 -25.5%
Non-residential, outside those hours 93 65 -28 -30.1%
Residential, all hours 558 631 +73 +13.1%
All AFA false alarms 891 823 -68 -7.6%

A fall in attendance, not in alarms. The records count incidents the Brigade attended. They cannot show how many alarms sounded in Redbridge and were not attended. For a non-exempt building in the policy hours, finding out why the alarm went off, and calling 999 if there is a fire, is now the building’s job. The counts here are small, so the percentages move a long way on a few incidents.

What building managers can do, for commercial buildings in the policy hours and for residential blocks.

Daytime non-residential attendances in Redbridge, month by month

Non-residential AFA false alarms attended between 07:00 and 20:30, Jan 2023 to Jul 2026.

  • Months before the change
  • Months after the change
Column chart of non-residential automatic fire alarm false alarms attended between 07:00 and 20:30 in Redbridge, by month from Jan 2023 to Jul 2026. 239 in the year before the change on 29 October 2024, 127 in the year after.010203040Jan 2023: 242023Feb 2023: 15Mar 2023: 21Apr 2023: 15May 2023: 18Jun 2023: 18Jul 2023: 16Aug 2023: 20Sep 2023: 19Oct 2023: 29Nov 2023: 25Dec 2023: 13Jan 2024: 272024Feb 2024: 27Mar 2024: 34Apr 2024: 17May 2024: 18Jun 2024: 12Jul 2024: 13Aug 2024: 15Sep 2024: 22Oct 2024: 18Nov 2024: 11Dec 2024: 13Jan 2025: 72025Feb 2025: 11Mar 2025: 13Apr 2025: 11May 2025: 10Jun 2025: 9Jul 2025: 9Aug 2025: 10Sep 2025: 10Oct 2025: 10Nov 2025: 7Dec 2025: 10Jan 2026: 122026Feb 2026: 15Mar 2026: 12Apr 2026: 11May 2026: 10Jun 2026: 3Jul 2026: 929 Oct 2024
Column chart of non-residential automatic fire alarm false alarms attended between 07:00 and 20:30 in Redbridge, by month from Jan 2023 to Jul 2026. 239 in the year before the change on 29 October 2024, 127 in the year after.010203040Jan 2023: 242023Feb 2023: 15Mar 2023: 21Apr 2023: 15May 2023: 18Jun 2023: 18Jul 2023: 16Aug 2023: 20Sep 2023: 19Oct 2023: 29Nov 2023: 25Dec 2023: 13Jan 2024: 272024Feb 2024: 27Mar 2024: 34Apr 2024: 17May 2024: 18Jun 2024: 12Jul 2024: 13Aug 2024: 15Sep 2024: 22Oct 2024: 18Nov 2024: 11Dec 2024: 13Jan 2025: 72025Feb 2025: 11Mar 2025: 13Apr 2025: 11May 2025: 10Jun 2025: 9Jul 2025: 9Aug 2025: 10Sep 2025: 10Oct 2025: 10Nov 2025: 7Dec 2025: 10Jan 2026: 122026Feb 2026: 15Mar 2026: 12Apr 2026: 11May 2026: 10Jun 2026: 3Jul 2026: 929 Oct 2024
Show the numbers as a table
Non-residential AFA false alarms attended between 07:00 and 20:30 in Redbridge, by month.
MonthAttendedPeriod
Jan 202324Before
Feb 202315Before
Mar 202321Before
Apr 202315Before
May 202318Before
Jun 202318Before
Jul 202316Before
Aug 202320Before
Sep 202319Before
Oct 202329Before
Nov 202325Before
Dec 202313Before
Jan 202427Before
Feb 202427Before
Mar 202434Before
Apr 202417Before
May 202418Before
Jun 202412Before
Jul 202413Before
Aug 202415Before
Sep 202422Before
Oct 202418Before (includes the first 3 days after)
Nov 202411After
Dec 202413After
Jan 20257After
Feb 202511After
Mar 202513After
Apr 202511After
May 202510After
Jun 20259After
Jul 20259After
Aug 202510After
Sep 202510After
Oct 202510After
Nov 20257After
Dec 202510After
Jan 202612After
Feb 202615After
Mar 202612After
Apr 202611After
May 202610After
Jun 20263After
Jul 20269After
Incidents attended, not alarm activations. Oct 2024 includes three days after the change and is shown as a “before” month. Source: London Fire Brigade Incident Records, London Datastore. Analysis: Gemini AMPM.
Where the alarms are · 2025

Mostly homes,
not workplaces.

Homes and other residential buildings account for 667 of the 851 (78.4%), and non-residential buildings for 21.6%, close to the London split. The property type with the most was “Self contained Sheltered Housing” (146, 17.2% of the borough total), followed by “House - single occupancy” (100). Across London the leading type is “Purpose Built Flats/Maisonettes - 4 to 9 storeys”.

Property types with the most AFA false alarms in Redbridge, 2025

Property type as recorded by London Fire Brigade crews. The percentage is the share of all AFA false alarms in the borough.

  • Residential
  • Non-residential
Bar chart of the property types with the most automatic fire alarm false alarms attended in Redbridge in 2025. Self contained Sheltered Housing is the largest with 146.Self contained Sheltered HousingSelf contained Sheltered Housing: 146 (17.2%)14617.2%House - single occupancyHouse - single occupancy: 100 (11.8%)10011.8%Purpose Built Flats/Maisonettes - 4 to 9 storeysPurpose Built Flats/Maisonettes - 4 to 9 storeys: 92 (10.8%)9210.8%Purpose Built Flats/Maisonettes - Up to 3 storeysPurpose Built Flats/Maisonettes - Up to 3 storeys: 77 (9.0%)779.0%Retirement/Old Persons HomeRetirement/Old Persons Home: 68 (8.0%)688.0%Purpose Built Flats/Maisonettes - 10 or more storeysPurpose Built Flats/Maisonettes - 10 or more storeys: 60 (7.1%)607.1%Secondary schoolSecondary school: 39 (4.6%)394.6%Infant/Primary schoolInfant/Primary school: 33 (3.9%)333.9%
Bar chart of the property types with the most automatic fire alarm false alarms attended in Redbridge in 2025. Self contained Sheltered Housing is the largest with 146.Self contained Sheltered HousingSelf contained Sheltered Housing: 146 (17.2%)14617.2%House - single occupancyHouse - single occupancy: 100 (11.8%)10011.8%Purpose Built Flats/Maisonettes - 4 to 9 storeysPurpose Built Flats/Maisonettes - 4 to 9 storeys: 92 (10.8%)9210.8%Purpose Built Flats/Maisonettes - Up to 3 storeysPurpose Built Flats/Maisonettes - Up to 3 storeys: 77 (9.0%)779.0%Retirement/Old Persons HomeRetirement/Old Persons Home: 68 (8.0%)688.0%Purpose Built Flats/Maisonettes - 10 or more storeysPurpose Built Flats/Maisonettes - 10 or more storeys: 60 (7.1%)607.1%Secondary schoolSecondary school: 39 (4.6%)394.6%Infant/Primary schoolInfant/Primary school: 33 (3.9%)333.9%
Show the numbers as a table
AFA false alarms attended in Redbridge in 2025, by property type (top eight).
Property typeCategoryAFA false alarms% of area total
Self contained Sheltered HousingDwelling14617.2%
House - single occupancyDwelling10011.8%
Purpose Built Flats/Maisonettes - 4 to 9 storeysDwelling9210.8%
Purpose Built Flats/Maisonettes - Up to 3 storeysDwelling779.0%
Retirement/Old Persons HomeOther Residential688.0%
Purpose Built Flats/Maisonettes - 10 or more storeysDwelling607.1%
Secondary schoolNon Residential394.6%
Infant/Primary schoolNon Residential333.9%
Incidents attended, not alarm activations. The eight property types with the most in 2025. A count by property type says where crews were sent, not what set the alarm off. Period: 1 January 2025 to 31 December 2025. Source: London Fire Brigade Incident Records, London Datastore. Analysis: Gemini AMPM.
In the league table

Next to Redbridge
in the ranking.

Buildings in Redbridge

If the alarms
are yours.

Gemini AMPM designs, installs, maintains and monitors fire alarm systems across London. Our fire alarm maintenance visits review the activation history each time, fire alarm monitoring puts a verification call between the panel and a 999 call, and remedial works covers the device and panel changes that remove a repeat cause.

Gemini AMPM in London: where we work and the sectors we work in. If false alarms are a problem in your building, tell us about it.

Data for Redbridge

Every figure on this page is in the borough table (CSV), with the same measures for all 33 areas and for London. Definitions and checks are on the methodology page.

This edition was generated on 5 October 2026 and covers incidents to 31 July 2026. The Index is refreshed when London Fire Brigade publishes new data.

Source and licence

Source: London Fire Brigade, London Fire Brigade Incident Records, published on the London Datastore (data.london.gov.uk). Contains public sector information licensed under the Open Government Licence v2.0. The Greater London Authority cannot warrant the quality or accuracy of the data. This analysis is by Gemini AMPM. It is not endorsed by, affiliated with or approved by London Fire Brigade or the Greater London Authority.